240v floormat 20a breaker wire gage 12 ok?

asked by john s. on 10/9/15

1 Answer
Thumbnail of user dmitryk3

Hi John,
Yes, it would be ok. However, the run should not be longer than 50ft, for full 20 Amp load. If run is longer, than 10AWG is recommended.
Thank you for interest in ThermoSoft floor heating technology. Please do not hesitate to call us at 800.308.8057 for further support.